Overview:
XBD vertical single-stage fire pump set is based on our IS type
pump, combined with the characteristics of foreign pipeline pump,
optimization design and manufacture of a new generation of products
by itself. Use of fire hydrants in the water, feeding sprinkler system water
supply in other occasions cleaning liquid.
Conditions of use:
1. XBD vertical single-stage fire pump set is used for transporting
ambient water.
2. The water does not contain corrosive substances and solid
particles.
3. Minimum working pressure 0.3Mpa, the maximum working pressure of
1.6 Mpa.Characteristics of XBD vertical single-stage fire pump products
4. The pump is a vertical structure, import and export of the same
caliber, and are in the same center line, as the valve can be
installed in the pipeline, compact appearance, small occupation
area, low construction inputs, such as protective cover can be
placed outdoors
5. The impeller mounted directly on the motor lengthened shaft,
short axial dimensions, compact structure, pump and motor bearings
reasonable configuration, can effectively balance the pump running
the radial and axial load, so as to ensure the operating balance
vibration noise of the pump is very low.
6. Seal mechanical seal mechanical seal or a combination, the use
of imported titanium alloy seal ring, medium and high temperature
mechanical seal with cemented carbide materials, wear-resistant,
can effectively increase the service life of mechanical seal.
Performance requirements of fire pump is:
1. Maximum flow fire pump shall be 150% of the value of the design,
the head is not less than the selected operating point of 65% lift,
lift off the pump when not greater than the selected operating
point of 140% lift, pump flow 1 2LS, head 1.1 - 1.2 times the fire
pump lift.
2. At the same time in the fire pump outlet pipe should be located
on measurement flowmeter, flow meter should be able to test 175% of
the pump flow rate selected, fire pump pressure gauge set should be
greater than 89mm in diameter at the outlet pipe.
| Product Name | Single stage fire pump |
| Scope Of Application | Mainly used for fire water supply, such as fire water supply for
various buildings, warehouses, airports, hotels, residential areas,
factories and other occasions. |
| Transport medium | Clear water |
| Flow range | 1-120L/S |
| Power range | 0.75-200kw |
| Head range | 20-150m |
| Material | Stainless steel,cast iron |